The summary is AI-generated and can contain mistakes. Always rely on the original Ministry report for decisions.
- GeneratorsEnvironment & safetyOrder
Inspectors found that the home has a generator that is available at all times, but it does not have the capacity to power all essential services and equipment required during a power outage. Specifically, the generator cannot power the heating system, food storage and meal preparation equipment, medication storage and preparation equipment, or life support and safety equipment for multiple residents.
- Maintenance ServicesEnvironment & safety
The home had schedules and procedures in place for generator maintenance, but staff did not follow the home's own Generator Policy. Inspectors found that daily checks of fuel, battery, and oil levels were not completed, monthly 60-minute load transfer tests were not performed, and a required semi-annual inspection by the service vendor did not occur.